DIMENSIONS AND ALLOWABLE OPERATIONAL MOVEMENT
Normal Pipe Size (in) |
1 | 1.25 | 1.5 | 2 | 2.5 | 3 | 4 | 5 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | 20 | 24 | 28 | 30 |
| |
| | | | | | | | | | | | | | | | | | |
| Neutral Length (in) |
6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 8 | 8 | 8 | 8 | 8 | 8 | 10 | 10 | 10 |
| |
| | | | | | | | | | | | | | | | | | |
Axial Compression (in) |
0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.625 | 0.625 | 0.625 | 0.625 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 |
| |
| | | | | | | | | | | | | | | | | | |
Axial Elongation (in) |
0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| |
| | | | | | | | | | | | | | | | | | |
Lateral Deflection (in) |
0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 |
| |
| | | | | | | | | | | | | | | | | | |
Angular Deflection (DEG) |
15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 10 | 10 |
Deflection Summary:
|
Compression
 |
Elongation
 |
Lateral
 |
Angular
 |
|
| |
| |
|
| OPERATING CONDITIONS |
| |
Working Pressure (PSI) |
225 | 225 | 225 | 225 | 225 | 225 | 225 | 225 | 225 | 225 | 225 | 225 | 142 | 142 | 142 | 142 | 142 | 114 | 114 |
| |
| | | | | | | | | | | | | | | | | | |
Burst Pressure (PSI) |
855 | 855 | 855 | 855 | 855 | 855 | 855 | 855 | 855 | 855 | 855 | 855 | 345 | 345 | 345 | 345 | 345 | 284 | 284 |
| |
| | | | | | | | | | | | | | | | | | |
Working Temperature (DEG F) |
220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 | 220 |
| |
| | | | | | | | | | | | | | | | | | |
Vacuum Rating (in HG) |
27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 |
| |
| |
|
| TYPICAL APPLICATIONS AND FLUIDS |
APPLICABLE FLUIDS:
Water, Warm Water, Sea Water, Weak Acids, Air
|
TYPICAL APPLICATIONS:
Pumps (Suction & Discharge Line) Air Conditioning, Ventilating, Chiller, Condenser Piping System, Sanitary, Irrigation Systems, Fire Fighting Systems, Hosereel Piping System, Marine Air Intake On Diesel Engines, Ballast Line
|
AVAILABLE FLANGE STANDARDS:
ANSI, BS10, BS4504, DIN, JIS AND SPECIAL SPECIFICATION (PLEASE REFER TO TABLE 4)
|
NOTES:
- Joints working under higher temperatures have a proportionally reduced pressure rating.
- Pressures shown are recommended operating pressures. Test pressure is 1.5 times "operating".
- Vacuum
Rating (in HG) is based on neutral installed length, without external load. Products should not be installed "elongated" on vacuum applications. AFA Style 99SFA expansion joints are furnished complete with retaining flanges.
- Because of storage space and shipping methods the (L) length of the joints mat vary from the dimension (L) above. This variance has no effect on the performance of the product. If the joint has been compressed or extended both can be manually extended and compressed to fit the measure space.
- AFA Style 99SFA permisible movements are shown in (Table 1A).
|
|